DISPLAYED PARAMETERS

Screen 1:
User Selectable

Screen 2: System voltage, average current,
total power

Screen 3: Voltage per
phase L-N,

Screen 4: Voltage per
phase to phase

Screen 5: Current per phase

Screen 6: System neutral current, frequency and
power factor

Screen 7: Power - kW (Active) and VAr (Reactive), kVA (Apparent)

Screen 8: kWh (Active energy)

Screen 9: kVAr.h (Reactive energy)

Screen 10: Demand A
and k W

Screen 11: Maximum
demand A and kW



Electrical power measurement, display and communication system

Applications include:

Low voltage switchgear and distribution
Process control/ monitoring
Energy and Building
Management Systems
Generator sets

FEATURES AND ADVANTAGES

 Measurement, display and
communication of up to 23 major parameters
 True RMS measurement for accurate  measurement of distorted waveforms
 High accuracies
 96 x 96mm DIN one piece self  contained package
 Ideal for retrofitting analogue switchboard meter applications
 Three line LED display
 Large red LEDs for easy viewing
 Tactile feedback keys for positive  user interface
 Simple menu structure
 User programmable screen for  custom applications
Designed to meet world-wide industry standard approvals, safety,
   performance, EMC, etc.

INPUT SPECIFICATION

Voltage:
57 - 277V L/N
100 - 480V L/L
Measuring Range 10 - 100%
Range of use 5 - 120%

Current:
5 amps (Standard) or
1 amp (Optional)
Measuring Range 10 - 100%
Range of use 5 - 120%
Maximum C.T. ratio 4000:5A
or 4000:1A

Frequency:
45 to 65Hz

Power Factor:
Range of use 0.5 Lag - 1 -0.8 Lead

Overloads:
Voltage:
2 x for 1 second (x10) at
10 second intervals
Maximum terminal voltage
1.2 times normal
Current:
20 x for 1 second (x5)
at 5 minute intervals
Maximum continuous terminal
current 1.2 times nominal

Burden:
Voltage: Each line <0.2VA
Current: Each phase <0.6VA

Isolation:
Input to Digital O/P.:
2.2kV
Input to Pulsed O/P.:
2.2kV
Dielectric voltage:
2.2kVV RMS 50Hz for 1 min withstand between circuits and accessible surfaces
Max. working voltage:
600V RMS between circuits
A.C. power surge voltage:
IEC 61000-4-5, 1.2/50 microseconds 4kV High frequency disturbance test:
IEC 61000-4-4, 2kVV peak all meas. inputs

Accuracy Class:
Voltage:
+0.4% of reading±0.1% of range
Current:
+0.4% of reading ±0.1%
of range Neutral +4% of range
Power:
kW kVA: +0.9 of reading
+0.1% of range kVAr: +1.9%
of reading ±0.1% of range
Energy:
kW.h 1% IEC 1036 (PF 0.8-1-0.8)
kVAr.h 2% IEC1036 (PF 0.8-1-0.8)
Frequency:
+0.15% of mid frequency
Phase/Power
Factor:
1% of unity
Climatic Temperature:
Operating 0 to 50°C
Storage -20 to +70°C Calibration 23°C
Temp Coeff:
±0.013%/°C (typical)
Humidity:
95% RH non condensing

Auxiliary Supply:
100 - 250V A.C./D.C.
Standard12 - 48V D.C. Optional

Approvals:
Production:
ISO 9001 certificate no. FM21540
Safety:
IEC 1010/BSEN 61010-1,
Installation category II pollution
degree 2, 600V RMS (General
electrical and mechanical safety
requirement) UL3111-1
Enclosure:
Production code IP54 BSEN60529,
IEC 529, BS5490, UL94V-0 Flame
retardant material
EMC:
Emissions BSEN50081/1,
Immunity BSEN50082/2
EU low voltage directive:
73/23/EEC amended by 93/68/EEC
EU EMC directive:
89/336/EEC amended by 93/68/EEC
Test Method:
Measuring circuit BSEN 60688, IEC688
BSEN 61036, IEC 1036 (kWh functionality)

Outputs (optional):
Digital: Ports:
1 off RS485 Modbus®, RTU Protocol 2 wire, half duplex, Screw clamp terminals
Alternatives:
LonWorks, Profibus DP, Devicenet
Pulsed Type Import Energy:
1 - Relay output SPNO 100V D.C. 0.5A